This object indicates the status of the breaker. A value of normal(1)
indicates the breaker is operating normally. A value of overloadWarning(2)
indicates the breaker has an overload warning. A value of overloadCritical(3)
indicates the breaker is overloaded. A value of voltageRangeWarning(4)
indicates the breaker voltage is out of tolerance by 10-20%. A value of
voltageRangeCritical(5) indicates the breaker voltage is out of tolerance
by more than 20%. Note: Overload status has priority over voltage tolerance
status.