cpqRackCommonEnclosureCondition
1.3.6.1.4.1.232.22.2.3.1.1.1.16
The overall condition of the enclosure.
This is the aggregate of the temperature sensors, fans, and
fuses within the enclosure.
This value will be one of the following:
other(1)
No temperature sensors, fans, or fuses in the enclosure or the
state could no be determined.
ok(2)
All temperature sensors, fans, and fuses are within the normal
operating range.
degraded(3)
One or more temperature sensors, fans, or fuses are outside of
the normal operating range. None are failed.
failed(4)
The temperature sensor exceeded the critical threshold value,
a required fan has failed, or a fuse has been tripped.
The system will automatically shutdown if the failed(4) condition
results, so it is unlikely that this value will ever be returned
by the agent.